KHS Flow-Splitter unit - dynamic, for flush mounted installation
figure 650 00
1. prevents stagnation in ring pipe installations through forced flow during downstream withdrawals, can be used in cold drinking water (PWC) and hot drinking water (PWH)
2. KHS Flow-Splitter - dynamic, according to the Venturi principle, including dynamic cartridge, flow and return branch for connection of outlets / plumbing units
3. wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
1. prevents stagnation in ring pipe installations through forced flow during downstream withdrawals, can be used in cold drinking water (PWC) and hot drinking water (PWH)
2. KHS Flow-Splitter - dynamic, according to the Venturi principle, including dynamic cartridge, flow and return branch for connection of outlets / plumbing units
3. wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
Product Features
- prevents stagnation in ring pipe installations through forced flow during downstream withdrawals, can be used in cold drinking water (PWC) and hot drinking water (PWH)
- KHS Flow-Splitter - dynamic, according to the Venturi principle, including dynamic cartridge, flow and return branch for connection of outlets / plumbing units
- wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
- KHS Flow-Splitter pass with female thread
- plumbing unit feed pipe with female thread
- plumbing unit return pipe with female thread
- maintenance free
- free from dead spots
- including quarter turn stop valves, female threaded, for flush-mounted installation, figure 585 00
- maintenance-free EPDM spindle seal
- plastic shaft can be shortened
- removable inner top part TOP-ENTRY, with EPDM gasket body and gunmetal ball
- incl. insulation shell
- for use in combination with DN 25 handle set
Standards and Approvals
- valve(s) with DVGW approval
- WRAS approval
- according to DVGW worksheet W 570
- according to accepted materials list from German environmental agency
- up to DN 32 soundproofing certification according to DIN EN ISO 3822 Class 1
- insulation shell building material class B1 according to DIN 4102
- DIN EN 13828
- ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT
Technical data
- max. installation depth 110mm
- pressure rating PN 16
- max. operating temperature 90°C
Part no. | passage DN |
Outlets DN |
VAV DN |
A1 | A2 | A3 | H1 (mm) |
L1 (mm) |
L2 (mm) |
L3 (mm) |
kg |
---|---|---|---|---|---|---|---|---|---|---|---|
6500001500 | 15 | 15 | 15 | Rp 1/2 | Rp 1/2 | Rp 1/2 | 48.5 | 185 | 100 | 84 | 1.81 |
6500002000 | 20 | 20 | 20 | Rp 3/4 | Rp 3/4 | Rp 3/4 | 58.5 | 185 | 100 | 90 | 2.23 |
6500022000 | 20 | 20 | 15 | Rp 3/4 | Rp 3/4 | Rp 1/2 | 58.5 | 185 | 100 | 84 | 2.03 |
6500002500 | 25 | 20 | 20 | Rp 1 | Rp 3/4 | Rp 3/4 | 68.5 | 185 | 100 | 90 | 2.48 |
6500022500 | 25 | 20 | 15 | Rp 1 | Rp 3/4 | Rp 1/2 | 68.5 | 185 | 100 | 84 | 2.35 |
6500003200 | 32 | 20 | 20 | Rp 1 1/4 | Rp 3/4 | Rp 3/4 | 73.5 | 195 | 100 | 90 | 2.57 |
6500023200 | 32 | 20 | 15 | Rp 1 1/4 | Rp 3/4 | Rp 1/2 | 73.5 | 195 | 100 | 84 | 2.45 |
6500004000 | 40 | 25 | 25 | Rp 1 1/2 | Rp 1 | Rp 1 | 78.5 | 206 | 100 | 99 | 3.77 |
6500024000 | 40 | 25 | 15 | Rp 1 1/2 | Rp 1 | Rp 1/2 | 78.5 | 206 | 100 | 84 | 2.99 |
6500044000 | 40 | 25 | 20 | Rp 1 1/2 | Rp 1 | Rp 3/4 | 78.5 | 206 | 100 | 90 | 3.15 |
6500005000 | 50 | 25 | 25 | Rp 2 | Rp 1 | Rp 1 | 88.5 | 219 | 100 | 99 | 4.39 |
6500025000 | 50 | 25 | 15 | Rp 2 | Rp 1 | Rp 1/2 | 88.5 | 219 | 100 | 84 | 3.69 |
6500045000 | 50 | 25 | 20 | Rp 2 | Rp 1 | Rp 3/4 | 88.5 | 219 | 100 | 90 | 3.88 |