FK-5 break tank station
figure 369 00
1. for the protection of drinking water against non-potable water of fluid category 5 in accordance with DIN EN 1717/DIN 1988-100
2. wetted parts on the drinking water side made of gunmetal, stainless steel and drinking water approved plastics
3. cover made of EPP
1. for the protection of drinking water against non-potable water of fluid category 5 in accordance with DIN EN 1717/DIN 1988-100
2. wetted parts on the drinking water side made of gunmetal, stainless steel and drinking water approved plastics
3. cover made of EPP
Product Features
- for the protection of drinking water against non-potable water of fluid category 5 in accordance with DIN EN 1717/DIN 1988-100
- wetted parts on the drinking water side made of gunmetal, stainless steel and drinking water approved plastics
- cover made of EPP
- easy operation using touch screen
- operating times can be defined
- flushing of the PWC line and cleaning of the container (optionally) possible
- readout of data, for example operating status and consumption figures, possible using USB interface
- high performance (flow rate and total head)
- for wall mounting or installation on optional rack
- rainwater utilisation can be integrated (optional)
- control of external immersion and metering pump possible
- low-noise operation
- normally closed inlet valve
- with coupling nut for flat sealing connection thread including EPDM gasket
- plastic drain connection according EN 1717
- frost protection monitor
- drain overflow monitoring (optional)
- BMS fault signal possible through a dry contact
- Connection to power supply with type F safety plug
- Connection to the pipe by enclosed flex pipe (500mm)
- discharge can be increased with a cascade setup (maximum three plants)
- maintenance requirements in accordance with DIN EN 806-5 must be complied
- aditional country-specific versions on request
- for further information on cascading, please contact your sales representative
Standards and Approvals
- DVGW approval
- KIWA approval
- plastic parts with KTW and W 270 approval
- according to accepted materials list from German environmental agency
- device cover building material class B2 in accordance with DIN 4102
- CE marking
Technical data
- pressure rating PN 10
- max. operating temperature 35°C
- min. ambient temperature 2°C
- max. ambient temperature 40°C
- protection class IP54
- power supply 230V AC
- volume of receiver tank 30 l
- Flushing volume of PWC line 10 l/min (at 3 bar)
- electrical power consumption DN 20 3.3 A/DN 25 5.5 A
- power factor 0.97
Part no. | DN | max. head (m) |
max. flow rate (m³/h) |
A1 | D1 (mm) |
H1 (mm) |
H2 (mm) |
L1 (mm) |
L2 (mm) |
L3 (mm) |
L4 (mm) |
T1 (mm) |
T2 (mm) |
T3 (mm) |
T4 (mm) |
minimum flow pressure (MPa) |
nominal connection diameter, waste water (mm) |
flow limiter in inlet | kg |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
3690002000 | 20 | 43.2 | 3 | G 1 | 75 | 994 | 930 | 600 | 110 | 94 | 206 | 330 | 215 | 147.6 | 9.5 | 0.10 | 75 | 50 | 43.6 |
3690002500 | 25 | 57.9 | 6 | G 1 1/4 | 75 | 994 | 930 | 600 | 110 | 94 | 206 | 330 | 215 | 147.6 | 9.5 | 0.15 | 75 | 100 | 47.4 |