Categories
MULTI-THERM thermostatic balancing valve
figure 141 0G
• control range 50°C - 65°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
• male union thread
MULTI-THERM thermostatic balancing valve, union thread, 50°C - 65°C
figure 143 00
• control range 50°C - 65°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
• female pipe thread
MULTI-THERM thermostatic balancing valve, FPT, 50°C - 65°C
figure 143 22
• control range 50°C - 65°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
• press connection for Geberit MAPRESS pipe
MULTI-THERM thermostatic balancing valve, MAPRESS, 50°C - 65°C
figure 041 0G
• control range 50°C - 65°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted parts made of stainless steel
• male union thread
SST MULTI-THERM thermostatic balancing valve, 50°C - 65 °C, union thread
figure 140 0G
• control range 30°C - 50°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
• male union thread
THERM thermostatic balancing valve, union thread, 30°C - 50°C
figure 142 00
• control range 30°C - 50°C
• thermostatic balancing valve for hydraulic balancing of riser and distribution pipes
• for hydraulic balancing of hot water return systems (PWH-C), supports thermal disinfection
• wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
• female pipe thread
THERM thermostatic balancing valve, FPT, 30°C - 50°C
- Stop Valves ꁕ
- Safety Valves ꁕ
- Pressure Reducing Valves and Filter
- Balancing valves ꁕ
- Measuring Products
- Hygiene System KHS ꁕ
- Thermal separators
- Flush-mounted valves
- Stop valves water meter combinations ꁕ
- Frost-proof outdoor taps
- TRESOR Cabinets ꁕ
- Sampling Valves
- ThermoSystem KTS ꁕ
- Other Valves
- Accessories ꁕ
-
Spare parts
ꁕ
- Spare parts for stop valves
- Spare parts for protection and safety valves
- Spare parts for pressure reducing valves and filters
- Spare parts for balancing valves
- Spare parts for measuring products
- Spare parts for sampling valves
- Spare parts for flush-mounted valves
- Spare parts for stop valve water meter models
- Spare parts for frost-proof outdoor taps
- Spare parts for TRESOR cabinets
- Spare parts for hygiene system KHS
- Spare parts for dirt traps
- Handwheels and gaskets
The MULTI-THERM automatically adjusts the hydraulic balancing depending on the temperature in circulation lines of the hot drinking water.
Circulation balancing valves must allow water to circulate at all times. Water must be able to continue to flow even after the target temperature is reached. Particularly for thermal disinfection, it is important for the water to be able to circulate continuously at a high temperature so that the circulation pump does not work against closed valves. These technical requirements are met by the MULTI-THERM.
With a factory setting of 58°C, the valve is fully open up to a valve temperature of approximately 53°C.
From 53°C pressure is lost due to the temperature-dependent cross-sectional change in the valve. When the target temperature reached, valve throttle position is set to its maximum, whereby a minimum volume constantly flows in the circulation system. The MULTI-THERM also supports the thermal disinfection.
Shut off, measure, drain
An immersion sleeve is integrated in the bonnet of the stop valve. A Pt 1000 temperature sensor (1) or a plug-in thermometer (2) can be used as an alternative to the attached handle. Temperature data can thus also be transmitted via the building management system or via the CONTROL-PLUS hand-held measuring device. Furthermore, a drain valve (3) can be installed on the MULTI-THERM to drain the line.
MULTI-THERM thermostatic balancing valve